43.4 GOT Side Settings

43.4.1
Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: PANASONIC
• Controller Type: Set according to the Controller
Type to be connected.
• PANASONIC MINAS-A4 series
• PANASONIC MINAS-A5 series
• I/F: Interface to be used
• Driver: PANASONIC MINAS
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

43.4.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
43.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Transmission
Speed
3.
Data Bit
4.
Stop Bit
Parity
Click!
Retry
Timeout Time
Host Address
Delay Time
POINT
POINT
POINT
(1) Communication interface setting by the Utility
(2) Precedence in communication settings
43. CONNECTION TO PANASONIC SERVO AMPLIFIER
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data
length used for communication
with the connected equipment.
(Default: 8bits)
Specify the stop bit length for
communications. (Default: 1bit)
Specify whether or not to perform a
parity check, and how it is
performed during communication.
(Default: None)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 3times)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the station No. of the servo
amplifier to connect the GOT.
(Default: 0)
Set this item to adjust the
transmission timing of the
communication request from the
GOT. (Default: 0ms)
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
43.4 GOT Side Settings
36
37
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
38
7bit/8bit
1bit/2bit
None
Even
Odd
39
0 to 5times
3 to 30sec
40
0 to 31
0 to 300ms
41
42
43
43 - 3