Mitsubishi Electric GT16 User Manual page 402

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

Error
Error message
code
Insufficient memory media
330
capacity. Confirm M-card
capacity.
Memory card not installed or
331
MCARD switched OFF
332 Memory media is not formatted.
Unable to overwrite. Memory
333
card is write-protected.
Memory media error. Replace
334
memory media.
Memory card battery voltage low.
335
Replace battery.
File output failed. Confirm output
337
file path.
BCD/BIN conversion error
345
Correct data
Recipe file error. Confirm content
351
of recipe file.
Recipe file make error. Reboot
352
GOT after inserting memory
card.
Unable to write Recipe file.
353
Confirm memory card is
inserted.
354 Recipe file write error
355 Recipe file read error
File system error occurred in
356
PLC. Confirm file register.
19 - 14
19. TROUBLESHOOTING
19.2 Error Message and System Alarm
Available memory of the CF card is insufficient.
Confirm the available memory of the CF card.
The available memory can be confirmed by system information screen,
which is described in GT Designer3 Version1 Screen Design Manual
(Fundamentals).
The CF card is not installed or in the drive access switch is OFF in
drive.
• Install the CF card in the specified drive.
• Turn ON the access switch.
CF card is not formatted or formatted incorrectly.
Format the CF card.
CF card is write-protected.
Cancel the write-protection of CF card.
CF card is faulty.
Replace the CF card.
The battery voltage of the CF card is low.
Replace the battery of the CF card.
Either of the following folder or file with the name same as the file to be
created exists in the storage destination CF card or USB memory.
• Folder storing data
• Write-protect file
Delete the above folder or file, or change the name of the file to be
created.
Any value that cannot be converted to a BCD/BIN value is being
displayed/input.
• Change the device data to be displayed to the BCD value.
• Correct the input value to the 4 digits integer.
The contents of the recipe file are not normal.
• Confirm the contents of the recipe files in the CF card or USB memory.
• Reboot the GOT after deleting the recipe file in the CF card or USB
memory (format).
Failed to generate recipe file.
Reboot the GOT after installing the CF card or USB memory.
Failed to write in the recipe file.
• Confirm the write-protection of the CF card or USB memory.
• Confirm the contents of the CF card or USB memory.
• Do not pull out the CF card or USB memory while recipe is
operating.
Error occurred while writing in the recipe file.
Do not unplug the CF card or USB memory while recipe is operating.
Error occurred while reading in the recipe file.
• Do not unplug the CF card or USB memory while recipe is operating.
• Confirm the contents (device value) of the recipe file in the CF card
or USB memory.
Error occurred in the specified file register when executing the recipe
function by specifying the file register name.
• Execute the recipe function again after confirming the file register
name.
• Execute the recipe function again after formatting the PC memory in
the specified PLC CPU drive with GX Developer.
Action
Channel No.