Connecting To Built-In Ethernet Port Cpu (Multiple Connection) - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

Checking communication state of Built-in
Ethernet port CPU
(1) When using the Command Prompt of Windows
Execute a Ping command at the Command Prompt of
®
Windows
.
(a) When normal communication
C:\>Ping 192.168.3.39
Reply from 192.168.3.39: bytes=32 time
<10ms TTL=32
(b) When abnormal communication
C:\>Ping 192.168.3.39
Request timed out.
(2) When abnormal communication
At abnormal communication, check the followings and
execute the Ping command again.
• Cable connecting condition
• Confirmation of switch and network parameter setting
• Operation state of PLC CPU (faulty or not)
• The IP address of Built-in Ethernet port CPU specified
in the ping command
POINT
POINT
POINT
Ethernet diagnostics of GX Works3
Ethernet diagnostics of GX Works3 is available to a
Ping test from the PLC.
For details of Ethernet diagnostics of GX Works3, refer
to the following manual.
Manuals of MELSEC iQ-R Series
Manuals of MELSEC iQ-F Series
22.4.2 Connecting to Built-in Ethernet
port CPU (multiple connection)
®
.
This section describes the settings of the GOT and Built-in
Ethernet port CPU in the following case of system
configuration.
POINT
POINT
POINT
Built-in Ethernet port CPU
For details of Built-in Ethernet port CPU, refer to the
following manual.
Manuals of MELSEC iQ-R Series
Manuals of MELSEC iQ-F Series
System configuration
(For MELSEC iQ-R Series)
*1
These setting items do not exist at the PLC side. However,
the virtual values must be set on the GOT side.
22. ETHERNET CONNECTION
[Controller Setting] and [Ethernet] of GT
Designer3
<GOT>
(The settings other than the
following are set to the default)
Network No.
PLC No.
IP address
: 192.168.0.18
Port No.
Communication
format
<Connecting to Built-in
1
Ethernet port CPU>
(The settings other than the
following are set to the default)
Network No.
: 1 (virtual)
PLC No.
: 2 (virtual)
IP address
: 192.168.0.1
Port No.
: 5006(fixed)
Communication
: UDP(fixed)
format
<Connecting to Built-in Ethernet port CPU>
2
(The settings other than the following are
set to the default)
Network No.
: 1 (virtual)
*1
PLC No.
: 3 (virtual)
*1
IP address
: 192.168.0.2
Port No.
: 5006(fixed)
Communication
: UDP(fixed)
format
[Module parameter] of GX Works3
■[Controller Setting] and [Ethernet] of GT Designer3
22.4 PLC Side Setting
20
21
22
23
: 1
: 1
: 5001
: UDP(fixed)
24
*1
*1
25
26
27
22 - 19