24.6 Device Range that Can Be Set
For details on the device range of controllers that can be
used on GT16 Handy, refer to the following manuals.
GT Designer3 Version1 Screen Design Manual
(Fundamentals)
GOT1000Series Connection Manual
(Mitsubishi Products) for GT Works3
24.7 Precautions
Station No. of inverter system
Make sure to establish inverter system with No.0
station.
Number of inverter
Up to 31 inverters can be connected.
Parameter setting
(1) Communication parameter change
Do not make any change for each communication
parameter of the inverter side from GOT.
If changed, the communication to the inverter cannot
be made.
(2) When setting "8888" or "9999" to inverter parameter
(Pr)
"8888" and "9999" designate special function.
When specifying from the GOT, it will be as follows.
Set value of inverter side
8888
9999
Screen switching devices, system
information devices
Make sure to use GD for screen switching devices and
system information devices when the GOT is
connected to only the inverter.
GOT clock control
Since the inverter does not have a clock function, the
settings of [time adjusting] or [time broad cast] by GOT
clock control will be disabled.
24 - 28
24. INVERTER CONNECTION
24.6 Device Range that Can Be Set
Value specified by GOT
65520
65535