24.5 FREQROL Series Inverter Side Settings

For details of the inverter, refer to the manual of each
series.
24.5.1 Connecting FREQROL-S500,
S500E, F500J series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection destination
RS-485 port
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit). Set Pr.30 (Extended function selection) to 1 [With
display] before making the parameter settings.
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Setting item
Parameter No.
Communication station
n1 (331)
number
*2
n2 (332)
Communication speed
*2
n3 (333)
Stop bit length
Parity check presence/
n4 (334)
*2
absence
Number of communication
n5 (335)
retries
Communication check time
n6 (336)
interval
Wait time setting
n7 (337)
CRLF selection
n11 (341)
*5
Protocol selection
Operation mode selection
Link start mode selection
n10 (340)
2
n12 (342)
E
PROM write selection
*1
Setting items are parameter names described in the manual
of FREQROL-S500, S500E, and F500J series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
When being monitored from the GOT, the parameter n1
through n7 correspond with Pr.331 through Pr.337, and the
parameter n10 through n12 correspond with Pr.340 through
Pr.342.
Numbers in brackets show the parameter number when the
parameter unit is in use.
*5
There is no Protocol selection setting on the inverter side.
24 - 16
24. INVERTER CONNECTION
24.5 FREQROL Series Inverter Side Settings
Parameters corresponding to inverter
Pr.79, n1 to n7, n10 to n12
Set
*4
Contents of setting
value
0 to 31
24.5.13 Station
number setting
*3
19200bps
192
Data length: 7bit
10
Stop bit length: 1bit
1
Odd
The inverter will not
---
come to an alarm
(65535)
stop.
Communication check
---
suspension
0
0ms
With CR
*3
1
Without LF
-
-
-
External operation
*3
Pr.79
0
mode at power on
Computer link
1
operation
Written to RAM and
*3
0
EEPROM
24.5.2 Connecting FREQROL-E500
series
Communication settings
Make the communication settings of the inverter.
Be sure to perform the inverter reset after updating
each parameter.
(1) Communication port and corresponding parameters
GOT connection
Parameters corresponding to inverter
destination
PU connector
Pr.79, Pr.117 to Pr.124, Pr.146, Pr.342
(2) Communication settings of inverter
Set the following parameters using the PU (parameter
unit).
Do not change these parameters, even though they
can be monitored from the GOT. If they are changed,
communication with the GOT is disabled.
*1
Parameter No.
Setting item
Communication station
number
*2
Communication speed
*2
Stop bit length
Parity check presence/
*2
absence
Number of communication
retries
Communication check time
interval
Wait time setting
CRLF presence/ absence
selection
*4
Protocol selection
Operation mode selection
Communication startup
*4
mode selection
2
E
PROM write selection
Frequency setting command
*5
selection
*1
Setting items are parameter names described in the manual
of FREQROL-E500 series.
*2
Settings on the GOT can be changed.
When changing the settings on the GOT, be sure to change
the parameters on the inverter to correspond with the GOT
settings.
*3
Inverter default values (No need to change)
*4
There is no Protocol selection setting on the inverter side.
*5
The setting is required for Frequency setting command
selection.
Set
Contents of setting
value
Pr.117
0 to 31
24.5.13 Station
number setting
*3
Pr.118
19200bps
192
Data length: 7bit
Pr.119
10
Stop bit length: 1bit
Pr.120
1
Odd
The inverter will not
9999
Pr.121
come to an alarm
(65535)
stop.
Communication
Pr.122
9999
check suspension
Pr.123
0
0ms
With CR
*3
Pr.124
1
Without LF
-
-
-
*3
Pr.79
PU operation mode
1
-
-
-
Written to RAM and
*3
Pr.342
0
EEPROM
Built-in frequency
setting
Pr.146
9999
potentiometer
invalid