Mitsubishi Electric GT16 User Manual page 409

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

Error
Error message
code
Cannot connect to SNTP Server.
616
Check the Server.
630 Failed to save a video file.
Failed to save a video file on
631
network.
An error occurred in a FTP client
640
process.
800 Abnormal module status
801 Abnormal baton passing status
Abnormal cyclic transmission
802
status
803 Transient error
The cable on the IN side is
804
disconnected or is not connected.
The cable on the OUT side is
805
disconnected or is not connected.
850 CC-Link switch setting error
Abnormal cyclic transmission
851
status
852 Abnormal host line status
853 Transient error
*1
When an error occurs, "FF
The settings for the SNTP server are wrong or the network to the SNTP
server is made up incorrectly.
• Check the operating conditions of the STNP server.
• Check the network to the SNTP server.
Check the CF card available area, installation status, cancellation of
write-protect, format status and number of saved files.
Check the activation status of personal computer linkage software in
file server, the setting of Ethernet FTP function of GOT, the network
setting of GOT and file server and the available area of CF card
installed in the GOT main unit.
Reconfigure the GOT (FTP client) setting.
Check the operating status and network line of the FTP server.
For the error details, check the GOT special register GS989 (FTP
communication error notification).
Refer to explanations of SB0020 on the applicable network manual.
Refer to explanations of SB0047 on the applicable network manual.
Refer to explanations of SB0049 on the applicable network manual.
Refer to explanations of SB00EE on the applicable network manual.
Refer to explanations of SB0067 on the applicable network manual.
Refer to explanations of SB0068 on the applicable network manual.
• Check if the switch settings have no error.
• Check error codes stored in SW006A.
• Refer to explanations of SB006A on the applicable network manual.
• Check if terminating resistors are connected.
• Check error codes for the PLC CPU.
• Check the parameter for the PLC CPU on the master station.
• Check the error status of the master station.
• Refer to explanations of SB006E on the applicable network manual.
• Check if the cable is unplugged or not.
• Refer to explanations of SB0090 on the applicable network manual.
• Check the transient error occurrence status for each station stored in
SW0094 to SW0097.
• Refer to explanations of SB0094.
" is stored to the channel No.
H
19.2 Error Message and System Alarm
Action
19. TROUBLESHOOTING
17
Channel No.
storage
18
19
19 - 21