51.4 GOT Side Settings

51.4.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YOKOGAWA
• Controller Type: YOKOGAWA GREEN/UT100/
UT2000/UTAdvanced
• I/F: Interface to be used
• Driver: YOKOGAWA GREEN/UT100/UT2000/
UTAdvanced
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

51.4.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
51 - 12
51. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
51.4 GOT Side Settings
3.
4.
Click!
[Controller Setting] from the
51.4.2 Communication detail settings
Item
Description
Set this item when change the
transmission speed used for
Transmission
communication with the connected
Speed
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the
Data Bit
connected equipment.
(Default: 8bits)
Specify the stop bit length for
Stop Bit
communications.
(Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
Parity
communication.
(Default: Even)
Set whether or not to perform a sum
Sum Check
check during communication.
(Default: No)
Set the number of retries to be performed
Retry
when a communication error occurs.
(Default: 0time)
Set the time period for a communication to
Timeout Time
time out. (Default: 3sec)
Specify the host address (station No. of
the GOT to which the temperature
Host Address
controller is connected) in the connected
network.
(Default: 1)
Set this item to adjust the transmission
Delay Time
timing of the communication request from
the GOT. (Default: 5ms)
Select the communication format.
(Default: 1)
Format 1:
Accessible to GREEN/UT100/UT2000/
Format
UTAdvanced Series
Format 2:
Accessible to GREEN/UT2000/
UTAdvanced Series, Not accessible to
UT100 Series.
POINT
POINT
POINT
(1) Format
• When connecting to UT100 Series, specify the
format 1.
• When connecting to only GREEN/UT2000/
UTAdvanced Series, specifying the format 2 is
recommended.
(2) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
(3) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
1bit/2bits
None
Even
Odd
Done, None
0 to 5times
3 to 30sec
1 to 99
0 to 300ms
1/2