(d) Setting of Transmission speed, Stop bit, Data bit,
Parity bit, Initializing method
Make the settings using the character configuration
switches.
Setting item
Set value
1
9600bps
ON OFF ON
Transmission
speed
19200bps
OFF ON
1bit
Stop bit
2bits
7bits
Data bit
8bits
Even
Odd
Parity bit
Done
None
Initializing
By switch
method
Switch No.
2
3
4
5
6
7
8
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Connecting to FFK120A-C10
(1) Communication settings
Make the communication settings using setting switches.
Item
Command-setting-type start-stop
synchronization, nonsequence format
RS-232C 1:1
Command-setting-type start-stop
synchronization, nonsequence format
*4
MODE
RS-232C 1:1,
and RS-485 1:N
Command-setting-type start-stop
synchronization, nonsequence format
RS-485 1:N
*1
9600bps, 19200bps
Transmission speed
*1
8bits or 7bits
Data bit
Even or Odd
*1
Parity bit
Done, None
*1
1bit, 2bits
Stop bit
Initializing method
By switch
*1*2
0 to 99
Station No.
*3
ON or OFF
Terminating resistor
T-link channel switch
T-link terminating resistor
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the station No. with any of the other units.
*3
Turn ON the terminating switch of a general-purpose interface
module which will be a terminal.
*4
Set as necessary.
(2) Settings by switch
Make the communication settings using each setting switch.
Character configuration
switches
Baudrate setting switch
MODE switch
T-link channel switch
T-link terminating resistor
ON/OFF switch
(a) Setting of the MODE
Make the MODE settings using the MODE switch.
MODE
Command-setting-type start-stop
synchronization, nonsequence format
RS-232C 1:1
Command-setting-type start-stop
synchronization, nonsequence format
RS-232C 1:1,
and RS-485 1:N
Command-setting-type start-stop
synchronization, nonsequence format
RS-485 1:N
47. CONNECTION TO FUJI PLC
47.2 Serial Connection
Set value
FUJI FA PLC user's Manual
RS-485 terminating resistor
ON/OFF switch
RS-485 station No.
switches
Switch position
1
2
3
47 - 15
44
45
46
47
48
49
50
51