29.4 GOT Side Settings

29.4.1 Setting communication
interface (Communication
settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: Set it according to the connected
equipment.
• Controller Type: Set it according to the connected
equipment.
• I/F: Interface to be used
• Driver: Multi-Drop (slave)
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

29.4.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
29.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Transmission Speed
3.
Retry
4.
Timeout Time
GOT Address
Click!
Delay Time
POINT
POINT
POINT
(1) Communication interface setting by Utility
(2) Precedence in communication settings
29. GOT MULTI-DROP CONNECTION
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 115200bps)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times
out.
(Default: 0time)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the station number of the
host station in the system
configuration.
(Default: 0)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
29.4 GOT Side Settings
28
29
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
30
0 to 5times
3 to 30sec
31
0 to 15
0 to 300ms
32
33
34
35
29 - 5

Advertisement