50.2.10 Connecting PC link module
(LC01-0N, LC02-0N)
Switch setting on the PC link module
Set the switches accordingly.
POINT
POINT
POINT
Switch setting
Set the switches before mounting the Ethernet
Interface Module on the base unit.
LC01-0N
Front
Rear
(1)
ON
OFF
1
2
(2)
3
4
5
6
7
8
(1) Transmission speed setting switch
Set the same transmission speed of the GOT.
*1
Setting
4
5
6
*1
Only transmission speeds available on the GOT side are
shown.
(2) Data format setting switch
Set the data length, parity, stop bit and checksum
consistent with the corresponding settings on the GOT
side.
l
Switch No.
1
Data bit
2
Parity
3
4
Stop bit
5
Checksum
End character
6
specification
7
Protect function
8
LC02-0N
Front
Rear
(1)
(3)
ON
OFF
STATION NO.
1
2
(2)
3
4
5
6
7
8
Transmission speed
4800bps
9600bps
19200bps
Description
Settings
ON (8bits),
OFF (7bits)
ON (done),
OFF (none)
ON (even),
OFF (odd)
ON (2bits),
OFF (1bit)
ON (done),
OFF (none)
OFF (none)
OFF (none)
-
OFF
(3) Station No. switch (LC02-0N only)
Rotary
Switch
Station No.
1)
(10's digit)
STATION NO.
Station No.
2)
(1's digit)
50. CONNECTION TO YOKOGAWA PLC
50.2 Serial Connection
Settings
RS-232
RS-422
Description
communi
communi
cation
cation
0
0
1
2
50 - 11