49.2.8 GOT Side Settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: YASKAWA
• Controller Type: Set either of the followings.
drdotGL/PROGIC8
• CP9200SH/MP900 series
• CP9200(H)
• CP9300MS (MC compatible)
• MP2000/MP900
• MP2000/MP900/CP9200SH series
• I/F: Interface to be used
• Driver: Set either of the following.
• YASKAWA GL/CP9200(SH/H)/CP9300MS
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
49.2.8 ■ Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
49 - 8
49. CONNECTION TO YASKAWA PLC
49.2 Serial Connection
Click!
[Controller Setting] from the
Communication detail settings
Make the settings according to the usage environment.
(1) YASKAWA GL/CP9200(SH/H)/CP9300MS
Item
Transmission
Speed
3.
Data Bit
4.
Stop Bit
Parity
Retry
Startup Time
Timeout Time
Host Address
Delay Time
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 19200bps)
Set this item when change the data
length used for communication with
the connected equipment.
(Default: 8bit)
Specify the stop bit length for
communications.
(Default: 1bit)
Specify whether or not to perform a
parity check, and how it is performed
during communication.
(Default: Even)
Set the number of retries to be
performed when a communication
error occurs.
(Default: 0time)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Specify the host address (station No.
of the PLC to which the GOT is
connected) in the network of the
GOT.
(Default: 1)
Set this item to adjust the
transmission timing of the
communication request from the
GOT.
(Default: 0ms)
Range
4800bps,
9600bps,
19200bps,
38400bps,
57600bps
8bit (fixed)
1bit (fixed)
Even (fixed)
0 to 5times
3 to 30sec
3 to 30sec
1 to 31
0 to 30
(
10 ms)