Got Side Settings; Setting Communication Interface (Communication Settings); Communication Detail Settings - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

40.4 GOT Side Settings

40.4.1 Setting communication interface
(Communication settings)
Set the channel of the equipment connected to the GOT.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: CHINO
• Controller Type: CHINO Controllers
• I/F: Interface to be used
• Driver: CHINO Controller(MODBUS)
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.

40.4.2 Communication detail settings

Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
40.4.2 Communication detail settings
Make the settings according to the usage environment.
Item
Transmission
Speed
3.
Data Bit
Stop Bit
4.
Parity
Retry
Timeout Time
Click!
Host Address
Delay Time
Format
POINT
POINT
POINT
(1) Format
(2) Delay Time
(3) Communication interface setting by the Utility
(4) Precedence in communication settings
40. CONNECTION TO CHINO CONTROLLER
Description
Set this item when change the
transmission speed used for
communication with the connected
equipment.
(Default: 9600bps)
Set this item when change the data length
used for communication with the
connected equipment. (Default: 8bits)
Specify the stop bit length for
communications. (Default: 1bit)
Specify whether or not to perform a parity
check, and how it is performed during
communication.
(Default: None)
Set the number of retries to be performed
when a communication error occurs.
(Default: 3times)
Set the time period for a communication to
time out. (Default: 1sec)
Specify the host address (station No. of
the GOT to which the controller is
connected) in the connected network.
(Default: 1)
Set this item to adjust the transmission
timing of the communication request from
the GOT. (Default: 5ms)
Select the communication format.
(Default: 1)
Format 1:
Accessible to LT230/300/400/830,
DZ1000/2000, Not accessible to GT120
Format 2:
Accessible to GT120
When connecting to GT120, specify format 2.
When connecting to the following models, set the
send delay time to 30ms or more.
Model name
DZ1000, DZ2000
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
40.4 GOT Side Settings
36
37
Range
9600bps,
19200bps,
38400bps,
57600bps,
115200bps
7bits/8bits
38
1bit/2bits
None
Even
Odd
0 to 5times
39
1 to 30sec
1 to 99
0 to 300ms
40
1/2
41
42
43
40 - 11

Advertisement

Table of Contents
loading

Table of Contents