33.3.2 GOT side settings

Setting communication interface
(Communication settings)
Set the channel of the connected equipment.
2.
1.
Select [Common]
[Controller Setting] from the
menu.
2.
The Controller Setting window is displayed. Select the
channel to be used from the list menu.
3.
Set the following items.
• Manufacturer: OMRON
• Controller Type: OMRON SYSMAC CS/CJ
• I/F: Interface to be used
• Driver: Ethernet (OMRON), Gateway
4.
The detailed setting is displayed after Manufacturer,
Controller Type, I/F, and Driver are set.
Make the settings according to the usage
environment.
33.3.2  Communication detail settings
Click the [OK] button when settings are completed.
POINT
POINT
POINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following.
17.1.2 I/F communication setting
Communication detail settings
Make the settings according to the usage environment.
Item
GOT NET No.
GOT PLC No.
GOT
IP address
3.
Subnet Mask
4.
Default
*1
Gateway
Ethernet
Download Port
*1
No.
GOT
Communication
*2
Port No..
Click!
Retry
Startup Time
Timeout
Time
Delay
Time
*1
*2
*3
33. CONNECTION TO OMRON PLC
Description
Set the network No. of the GOT.
(Default: 1)
Set the station No. of the GOT.
*3
(Default: 1)
Set the IP address of the GOT.
*1
(Default: 192.168.3.18)
Set the subnet mask for the sub
network. (Only for connection via
*1
router) If the sub network is not used,
the default value is set.
(Default: 255.255.255.0)
Set the router address of the default
gateway where the GOT is
connected. (Only for connection via
router)
(Default: 0.0.0.0)
Set the GOT port No. for Ethernet
download.
(Default: 5014)
Set the GOT port No. for the
connection with the Ethernet module.
(Default: 5018)
Set the number of retries to be
performed when a communication
timeout occurs.
When receiving no response after
retries, the communication times out.
(Default: 3times)
Specify the time period from the GOT
startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination PLC.
(Default: 0ms)
Click the [Setting] button and perform the setting in the [GOT
IP address settings] screen.
If the [IP address conversion method] for the OMRON PLC
setting is other than [Automatic conversion
method(dynamic)], set the same [GOT Communication Port
No.] setting as that of [FINS UDP Port] of CX-Programmer.
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
33.3.2  Ethernet setting
33.3 Ethernet Connection
28
Range
1 to 127
1 to 254
29
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
30
0.0.0.0 to
255.255.255.255
1024 to 5010,
5014 to 65534
(Except for 5011,
5012 and 5013)
1024 to 5010,
31
5015 to 65534
(Except for 5011,
5012 and 5013)
0 to 5times
32
3 to 255sec
3 to 90sec
0 to 10000
33
(
10 ms)
34
35
33 - 23