(2) Communication mode settings
Make this setting by operating the communication
mode select DIP SW.
Switch position
Communication mode
ON
PC link communication mode
(3) A setting of the station No.
Make this setting by operating the station No. select
Rotary switch.
Switch position
Station No.
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
A
11
B
12
C
13
D
14
E
15
F
16
51.5.4 Connecting to UTAdvanced
Series
Communication settings
Make the communication settings by operating the key of the
temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
*1
7bits, 8bits
Data bit
*1
Even, odd, none
Parity bit
*1
1bit, 2bits
Stop bit
*1*2
1 to 99
Address
Minimum response time
0 to 10 ( 10ms)
PCL(0): PC link communication (without
sum check)
*1
Protocol selection
PCLSM(1): PC link communication (with
sum check)
*1
Adjust the settings with GOT settings.
*2
Avoid duplication of the address with any of the other units.
51 - 14
51. CONNECTION TO YOKOGAWA TEMPERATURE CONTROLLER
51.5 Temperature Controller Side Setting
ON
OFF
Set value
51.5.5 Connecting to converter (ML2-
[ ])
Communication settings
Make the communication settings using setting switches.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
*2
2-wire type or 4-wire type
Setting (2-wire/4-wire)
*2
With, Without
Terminating resistor
Echo back
OFF
RS-485 driver-active control
AUTO
*1
Adjust the settings with GOT settings.
*2
Refer to the following connection diagram for setting.
51.3.2 RS-485 cable
Settings by switch
Timer change-over time
Rotary switch
Communication setting
DIP SW
(1) Settings of the setting (2-wire/4-wire), the RS-485 driver-
active control, the terminating resistor, the echo back
Make those settings by operating the communication setting
DIP SW.
Set
Setting item
value
4-wire
type
Setting(2-wire/4-wire)
2-wire
type
RS-485 driver-active control
AUTO
with
Terminating resistor
without
Echo back
OFF
(2) A setting of the transmission speed
Make this setting by operating the timer change-over
time Rotary switch.
Switch position
Transmission speed
5
9600bps
6
19200bps
7
38400bps
Set value
Switch position
1
2
3
4
5
OFF OFF
ON
ON
OFF
ON
OFF
OFF