Ethernet Setting - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

(2) Ethernet(MELSEC), Q17nNC, CRnD-700
Item
Description
Set the network No. of the GOT.
GOT NET No.
(Default: 1)
Set the station No. of the GOT.
*2
GOT PLC No.
(Default: 1)
GOT
Set the IP address of the GOT.
*1
(Default: 192.168.3.18)
IP Address
Set the subnet mask for the sub
network. (Only for connection via
router)
*1
Subnet Mask
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
Default
connected. (Only for connection via
Gateway
router)
*1
(Default: 0.0.0.0)
Ethernet
Set the GOT port No. for Ethernet
Download Port
download.
*1
(Default: 5014)
No.
Set the GOT port No. for the
GOT
connection with the Ethernet
Communication
module.
Port No.
(Default: 5001)
Set the number of retries to be
performed when a communication
timeout occurs.
Retry
When receiving no response after
retries, the communication times
out.
(Default: 3times)
Specify the time period from the
GOT startup until GOT starts the
Startup Time
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
Timeout Time
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
Delay Time
PLC.
(Default: 0ms)
*1
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting]
screen.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.

27.4.3 Ethernet setting

POINT
POINT
POINT
Range
(1) Communication interface setting by Utility
1 to 239
1 to 64
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
(2) Precedence in communication settings
0.0.0.0 to
255.255.255.255
27.4.3 Ethernet setting
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
0 to 5times
Item
Host
N/W No.
3 to 255sec
PLC No.
3 to 90sec
Type
0 to 10000
(
10 ms)
IP Address
Port No.
Communication
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For the details on the Utility, refer to the following
manual.
12. COMMUNICATION INTERFACE SETTING
(COMMUNICATION SETTING)
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Description
The host is displayed.(The host
is indicated with an asterisk (*).))
Set the network No. of the
connected Ethernet module.
(Default: blank)
Set the station No. of the
*2
connected Ethernet module.
(Default: blank)
Set the type of the connected
Ethernet module.
(Default: QJ71E71)
Set the IP address of the
connected Ethernet module.
(Default: blank)
Set the port No. of the connected
Ethernet module.
(Default: 5001)
UDP (fixed)
*1
For operating CNC monitor function, set N/W No. to "239".
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
27.4.2 Communication detail settings
27. CNC CONNECTION
27.4 GOT Side Settings
20
21
22
23
24
Range
-
Network No. of
*1
CNC
Station No. of
25
CNC
AJ71QE71
IP address of CNC
26
5001
UDP (fixed)
27
27 - 5