Ethernet adapter module setting
Set the parameter with the Ethernet adapter unit setting
tool.
(1) CC-Link IE Field Network setting
Item
Network No.
Station No.
*1
Set the same value as the network No. set on the PLC side.
*2
Set a value other than the network No. set on the PLC side.
(2) Ethernet setting
Item
IP address
*1
Set the IP address within the following range.
192.168. 3. 30
Set the fourth octet within the range from 1 to 64.
Set the third octet within the range from 1 to 239.
22 - 52
22. ETHERNET CONNECTION
22.4 PLC Side Setting
Set value
*1
1
*2
1
Set value
*1
192.168.3.30
[Controller Setting] and [Ethernet] of GT
Designer3
POINT
POINT
POINT
[Controller Setting] and [Ethernet] of GT Designer3
For [Controller Setting] and [Ethernet] of GT
Designer3, refer to the following.
22.3.1 Setting communication interface
(Communication settings)
(1) Controller setting
Item
GOT NET No.
GOT PLC No.
GOT IP Address
GOT Port No. (Communication)
GOT Port No. (Ethernet Download)
Default Gateway
Subnet Mask
Retry
Startup Time
Timeout Time
Delay Time
*1
Set the GOT network No. according to the third octet
(network No.) of the Ethernet adapter unit IP address.
(2) Ethernet setting
Item
Host
N/W No.
PLC No.
Ethernet
Type
setting No.1
IP address
Port No.
Communication
*1
Set according to the third octet (network No.) of the Ethernet
adapter unit IP address.
*2
Set according to the fourth octet (PC No.) of the Ethernet
adapter unit IP address.
*3
Set according to the Ethernet adapter unit IP address.
(3) Routing parameter setting
Item
Target network No.
Relay network No.
Relay station No.
*1
Set the same value as the Ethernet adapter unit network No.
*2
Set according to the third octet (network No.) of the Ethernet
adapter unit IP address.
*3
Set according to the fourth octet (PC No.) of the Ethernet
adapter unit IP address.
Setting (Use default value.)
*1
3
1
192.168.3.18
5001
5014
0.0.0.0
255.255.255.0
3times
3sec
3sec
0ms
Set value
*
*1
3
*2
30
NZ2GF-ETB
*3
192.168.3.30
5001 (fixed)
UDP (fixed)
Range
*1
1
*2
3
*3
30