Setting Of Energy Measuring Unit/Electric Multi-Measuring Instrument; Connecting To An Energy Measuring Unit/Electronic Multi-Measuring Instrument; Station Number Setting - Mitsubishi Electric GT16 User Manual

Got1000 series
Hide thumbs Also See for GT16:
Table of Contents

Advertisement

28.5 Setting of Energy Measuring Unit/Electric Multi-
measuring Instrument
POINT
POINT
POINT
Energy measuring unit/electric multi-measuring
instrument
For details of the energy measuring unit/electronic
multi-measuring instrument, refer to the following
manual.
Series
EMU4-BD1-MB
Energy measuring unit
EMU4-HD1-MB
Electric multi-measuring
ME110SSR-MB
instrument
28.5.1 Connecting to an energy
measuring unit/electronic
multi-measuring instrument
Communication settings
Make the communication settings with the front
operation switch on the energy measuring unit/
electronic multi-measuring instrument.
Item
*1*2
9600bps, 19200bps, 38400bps
Transmission speed
Data Bit
8bits (Fixed)
1bit, 2bits
*2
Stop Bit
(Default: 1bit)
NONE/EVEN/ODD
*2
Parity
(Default: EVEN)
1 to 247
*2
Device address
(Default: 1)
*1
Indicates only the transmission speeds that can be set on
the GOT side.
*2
Adjust the settings with GOT settings.
28 - 4
28. ENERGY MEASURING UNIT/ELECTRIC MULTI-MEASURING INSTRUMENT CONNECTION

28.5 Setting of Energy Measuring Unit/Electric Multi-measuring Instrument

Model name
Refer to
28.5.1
Set value

28.5.2 Station number setting

In the MODBUS network, a maximum of 31 energy
measuring units/electronic multi-measuring instruments
can be connected to 1 GOT.
Assign a non-overlapped station number ranging from 1 to
247 arbitrarily to each energy measuring unit/electronic
multi-measuring instrument.
In the system configuration, the energy measuring unit/
electric multi-measuring instrument with the station number
set with the host address must be included. The station
number can be set without regard to the cable connection
order. There is no problem even if station numbers are not
consecutive.
Station
GOT
No.3
Examples of station number setting
Station
Station
No.15
No.1

Advertisement