49.3.4 PLC side setting (CP-9200SH
series, CP-312 series)
POINT
POINT
POINT
YASKAWA PLC
For details of YASKAWA PLCs, refer to the following
manuals.
YASKAWA PLC user's Manual
Parameter settings
Make the parameter settings with a peripheral tool.
Settings for CP-218IF
Item
Module Type
CPU Number
Circuit Number
Hot Swapping
Item
CNO 03
Local Port
10500
Node IP
192.168.001.018
*1
Address
*1
05016
Node Port
Connection
TCP
Type
Protocol
Extended
Type
MEMOBUS
Code
BIN
*1
Be sure to set the values above for the address so that the
GOT communicates with the programmable controller
correctly.
For the Host Address setting on the GOT side, refer to the
following.
49.3.2 ■ Ethernet setting
Set value
CP-218
01
01
CNO 04
CNO 05
10501
10030
192.168.001.020
192.168.001.073
05017
21001
TCP
UDP
Extended
Extended
MEMOBUS
MEMOBUS
BIN
BIN
49. CONNECTION TO YASKAWA PLC
49.3 Ethernet Connection
44
45
46
47
48
49
50
51
49 - 19