Delta AS Series Programming Manual page 827

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

AS Ser ies Pro gra mm in g M anu al
Example
When X0.0 is ON, the BIN instruction converts the binary-coded decimal value in X1.15–X1.0 into the binary value, and
stores the conversion result in D0. The FLT instruction converts the binary value in D0 into a floating-point number, and
stores the conversion result in (D11, D10). The FRAD instruction converts a floating-point number in (D11, D10) into
radians, and stores the conversion result in (D21, D20). The FSIN instruction finds the sine of the radian value in (D21,
D20), and stores it in (D31, D30). The sine value is a floating-point number.
X1.15~X1.0
0 0
9
0
_6
Binary -coded
decimal value
F RAD
Additional remarks
1.
If the value in S exceeds the range of values that can be represented by floating-point numbers, the instruction is
not executed, SM0 is ON, and the error code in SR0 is 16#2013.
2.
If SM695 is ON, and the value in S is not between 0–360, the instruction is not executed, SM0 is ON, and the error
code is 16#2003.
6 - 5 4 8
BIN
D0
F LT
90
Binary val ue
F SIN
D21~D20
R1.570796
F loating- point
number
D11~D10
R90
F loating- point
number
D31~D30
R1
F loating- point
number

Hide quick links: