DDRVI outputs 20,000 pulses in the positive direction. Note: the instruction does not output in the
positive direction if the positive limit point is ON when the function starts.
When the limit input point X0.6 is triggered by the external mechanism and is ON, the condition for the
hardware positive limit function is met.
DDRVI instruction stops the output immediately and the positive limit alarm SM465 is ON.
If the condition for the hardware limit function is not met, Y0.0 stops the output after 20,000 pulses.
c)
Operation of the negative limit
Negative limit input point X0.7 is set in HWCONFIG and is downloaded to PLC. When SM466 is set to ON,
the negative limit function starts.
DDRVI outputs 20,000 pulses in the negative direction. Note: the instruction does not output in the negative
direction if the negative limit point is ON when the function starts.
When the limit input point X0.7 is triggered by the external mechanism and is ON, the condition for the
hardware negative limit function is met.
DDRVI instruction stops the output immediately and the negative limit alarm SM467 is ON.
If the condition for the hardware limit function is not met, Y0.0 stops the output after -20,000 pulses.
d)
SM flags related to the limit function
_6
Axis number
Enabling the
hardware positive
limit
Positive limit alarm
flag
Enabling the
hardware negative
limit
Negative limit alarm
flag
Note: The limit point alarm flag is read-only and is set or reset automatically by the PLC according to the state of
the start flag.