AS Ser ies Pro gra mm in g M anu al
 DDRVI outputs 20,000 pulses in the positive direction. Note: the instruction does not output in the
positive direction if the positive limit point is ON when the function starts.
 When the limit input point X0.6 is triggered by the external mechanism and is ON, the condition for the
hardware positive limit function is met.
 DDRVI instruction stops the output immediately and the positive limit alarm SM465 is ON.
 If the condition for the hardware limit function is not met, Y0.0 stops the output after 20,000 pulses.
c)
Operation of the negative limit
 Negative limit input point X0.7 is set in HWCONFIG and is downloaded to PLC. When SM466 is set to ON,
the negative limit function starts.
 DDRVI outputs 20,000 pulses in the negative direction. Note: the instruction does not output in the negative
direction if the negative limit point is ON when the function starts.
 When the limit input point X0.7 is triggered by the external mechanism and is ON, the condition for the
hardware negative limit function is met.
 DDRVI instruction stops the output immediately and the negative limit alarm SM467 is ON.
 If the condition for the hardware limit function is not met, Y0.0 stops the output after -20,000 pulses.
d)
SM flags related to the limit function
_6
Axis number
Enabling the
hardware positive
limit
Positive limit alarm
flag
Enabling the
hardware negative
limit
Negative limit alarm
flag
Note: The limit point alarm flag is read-only and is set or reset automatically by the PLC according to the state of
the start flag.
6 - 9 1 4
Axis 1
Axis 2
SM464
SM484
SM465
SM485
SM466
SM486
SM467
SM487
Axis 3
Axis 4
SM504
SM524
SM505
SM525
SM506
SM526
SM507
SM527
Axis 5
Axis 6
SM544
SM564
SM545
SM565
SM546
SM566
SM547
SM567