Example 1:
1.
Enable the mechanical unit conversion function
2.
Set the position planning table and download the parameters
The target position is 2000 (Unit:mm). After converting in the position planing table, 400,000 output pulses are
downloaded and saved in the PLC.
When M0 is ON, Y0.0 outputs 400,000 pulses at 100kHz. After the output completes, M100 is ON.
Example 2: Use global symbol or D device in Target Position
1.
Use D device in Target Position of the position planning table and download the parameters.
The unit for D60 in PLC is pulse by default. If you need to use D devices in Target position and in the
mechanical unit, you need to convert the mechanical unit to pulse.
2.
When M0 is ON, and D60 is 400,000. Y0.0 outputs 400,000 pulses at 100kHz. After the output completes,
M100 is ON.
Note: the unit is pulse, when you use global symbols, D devices, or instructions including DTPWS, DTPWL,
and DTPWC to input values in in Target Postion.
Cha p ter 6 App l ied Ins truc tio ns
6_
6 - 9 6 9