Destinati on value
Maximum destination
value
=500
D
Minimum des ti nation
value
=30
0
Example 2
1.
Suppose the value in S
the maximum destination value in D2 is 30, and the minimum destination value in D3 is 500. When X0.0 is ON, the
SCLP instruction calculates the scales value, and stores it in D10.
2.
The operation equation: D10=[(500–200)×(30–500)]÷(3,000–200)+500=449.64
449.64 is rounded off to the nearest whole digit, and becomes 450. 450 is stored in D10.
=500
S
1
Maximum
Minimum
sourc e value
sourc e value
=200
is 500, the maximum source value in D0 is 3,000, the minimum source value in D1 is 200,
1
Ch a pt er 6 A pp l i e d I n s tr uc t io ns
Sourc e value
=3000