Delta AS Series Programming Manual page 449

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

AS Ser ies Pro gra mm in g M anu al
API
Instruction code
0504
Device
X
S
Data
type
S
Symbol
Explanation
1.
The data source S can contain only decimal numbers, and the number must be an interrupt number. If the number
in S is not an interrupt number, the instruction is not executed and no warning is shown. For example, use DIX500
when you want to disable the I500 interrupt. Refer to the interrupt number list in the explanation of the EI
instruction.
_6
2.
The default for interrupt tasks in the AS Series is enabled. Use the DIX instruction to disable the interrupts.
3.
You can use this instruction to disable the interrupt tasks in SR623–SR634.
4.
If this instruction is not executed, then the contents of SR623–SR634 determine whether an interrupt task is
performed or not.
5.
Refer to the examples for the EI instruction (API 0501) for more information.
6 - 1 7 0
DIX
Y
M
S
T
C
Operand
S
HC
D
FR
SM
Pulse instruction
16-bit instruction
S
Data source
Function
Disabling a specific interrupt
SR
E
K
16#
"$"
32-bit instruction
AS
F

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents