AS Ser ies Pro gra mm in g M anu al
3.
If the string in S is out of range, the instruction is not executed, SM is ON, and the error code in SR0 is 16#2003.
If the first character in the string is a number "0"–"9" (16#30–16#39), the valid range for a floating-point string
is 1–24. The minimum length for the string is one.
If the first character in the string is a blank (16#20) or a sign ("+"(16#2B) or "-" (16#2D)), the valid range for a
floating-point string is 2–24. The minimum length for the string is two ("+1").
4.
If the conversion result exceeds the range of values that can be represented by floating-point numbers, the
instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2013.
_6
6 - 7 7 0