Delta AS Series Programming Manual page 755

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

AS Ser ies Pro gra mm in g M anu al
Operand
PID_RUN
SV
PID_MODE
_6
PID_MAN
MOUT_AUTO
AUTO_DBW
6-476
Data type
BOOL
Enabling the PID algorithm
DWORD/DINT
Target value
DWORD/DINT
PID control mode
BOOL
PID A/M mode
BOOL
MOUT automatic change mode
Range within which the auto
DWORD/DINT
tuning is not working
Function
Setting range
True: use the PID algorithm.
False: reset the output value (MV) to
0, and stop using the PID algorithm.
-32768~32767
0: Automatic control
When PID_MAN switches from True
to False, invoke the output value
(MV) in the automatic algorithm.
1: Auto tuning the parameters for the
temperature control. After tuning is
done, the system is in auto control
mode (PID_MODE is set to 0) and
fill in the appropriate parameters
(Kc_Kp, Ti_Ki, Td_Kd, Tf, APPHA
and BETA)
Note: when the mode is set to 1, auto
True: Manual
False: Automatic
True: Automatic
False: Normal
0~32000
Description
Target value
tuning the parameter, you
cannot set up the value.
Output the MV according to
MOUT. This setting has no
effect when PID_MODE is set to
1.
Output the MV according to the
PID algorithm.
MOUT value varies with the MV.
MOUT value does not vary with
the MV.
Auto tuning NOT
activated when