AS Ser ies Pro gra mm in g M anu al
2.
When you enable this instruction for the first time, it sends the communication command. If the number of
connected slaves reaches the upper limit, the communication status value in D
command is not sent. The error code shows16#6306 in D
3.
When the parameter exceeds the range, the instruction is not executed and the communication status value in D
is 4.
4.
This instruction should work with rising-edge trigger. If it is repeatedly triggered, the error code shows16#02 in
D
[0]. Wait till the execution of the instruction is complete before starting another instruction.
2
Example 1
The instruction reads the vendor code of the device at 192.168.1.5 and stores the value in D100. It sets the EtherNet/IP
Object parameters as shown below.
(1)
Class ID = 1
(2)
Instance ID = 1
(3)
Attribute ID = 1
_6
_6
6 - 8 2 6
is 3, and the communication
1
[1] .
2
1