AS Ser ies Pro gra mm in g M anu al
6.
If the communication command is 0x05 or 0x06, the value in n can be ignored. The length of the data is only one
bit or one word.
7.
The MODRW instruction is not executed if the sending flags SM96 and SM97 are not ON.
8.
If a communication timeout occurs, the timeout flags SM104 and SM105 are ON, and the receiving flags SM98 and
SM99 are OFF.
9.
If an error occurs while receiving data, the error flags SM102 and SM103 are ON, and the receiving flags SM98
and SM99 are OFF.
10.
If the function code specified by S
PLC communicates must be a word device. If the function code specified by S
in the external equipment with which the PLC communicates must be a bit device.
11.
Please refer to section 6.19.3 for more details on communication register setups (SM, SR).
_6
6 - 6 5 4
is related to word devices, the device in the external equipment with which the
2
is related to bit devices, the device
2