AS Ser ies Pro gra mm in g M anu al
API
Instruction code
0701
Device
X
D
n
Data
type
D
n
Symbol
Explanation
1.
This instruction uses seconds as the unit of time. The time for which a button switch has been turned ON is
multiplied by n, and the product is stored in D. D+1 is for system use only. When the instruction is executed, the
value in D+1 cannot be altered. Otherwise, the time is counted incorrectly.
_6
2.
When the conditional contact is ON, D is reset to 0.
3.
Setting the multiplier: when n is 0, D uses a second as the timing unit. When n is 1, the time for which the button
switch has been turned ON is multiplied by 10, and D uses 100 milliseconds as the timing unit. When n is 2, the
time for which the button switch has been turned ON is multiplied by 100, and D uses 10 milliseconds as the timing
unit. The greater the value in n, the higher the timing resolution.
4.
When you use on-line editing, reset the conditional contact to initialize the instruction.
5.
The value in n must be between 0–2.
6 - 1 8 2