6.
Software limit function
a)
The following diagram shows the output curve diagram of axis 1 (Y0.0/Y0.1).
Positive limit function
b)
Operation of the positive limit
Positive software limit position is set in HWCONFIG (by setting SR580=11,000 for example). After downloading
the setting to the PLC, it means the positive limit function starts.
DDRVI starts to output 20,000 pulses in the positive direction. Note: the instruction does not output in the
positive direction if the positive limit is exceeded when the function starts.
When the current position SR460 > the limit position SR580, it means that the condition for the software limit
function is met.
DDRVI instruction stops the output immediately and the positive limit alarm SM465 is ON.
If the condition for the limit function is not met, Y0.0 stops the output after 20,000 pulses.