AS Ser ies Pro gra mm in g M anu al
API
Instruction code
0702
Device
X
S
m
D
Data
type
S
m
D
Symbol
Explanation
_6
1.
This instruction generates timing for the off-delay relay, the one-shot circuit, and the flashing circuit.
2.
This instruction uses 100 milliseconds as the timing unit. If the setting value for m is 50, the time value is 5
seconds.
3.
You cannot use this timer repeatedly.
4.
D occupies four consecutive devices.
5.
Before the instruction is executed, reset D-D+3.
6.
When the conditional contact is not enabled and the value of the device meets one of the two conditions mentioned
below, D, D+1, and D+3 are ON for m seconds before they are switched OFF. When the conditional contact is not
enabled and the value of the device does not meet either of the two conditions mentioned below, D-D+3 keep OFF.
The value of the timer is less than or equal to m, D is ON, and D+1 is OFF.
The value of the timer is less than m, D +2 is OFF, and D, D+1, and D+3 are ON.
7.
When the on-line editing is used, Reset the conditional contact to initialize the instruction.
8.
The value in m must be between 1–32767.
6 - 1 8 4
STMR
Y
M
S
T
C
Operand
S, m, D
HC
D
FR
SM
Pulse instruction
16-Bit instruction
: Timer number (T0-T511)
S
m : Setting value of the timer
: Output device
D
Function
Special timer
SR
E
K
16#
"$"
32-Bit instruction
AS
F