Delta AS Series Programming Manual page 1014

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

2.
If the product serial no. is AS332T-AW16360001, the reading code of the instruction is 0 and the read data are
stored in the devices starting from D0, the product serial no. is stored in the order as below.
D0
D1
16#5341
16#3333
'SA'
'33'
3.
If Mac ID is 16#123456789ABC, the reading code of the instruction is 1 and the read data are stored in the devices
starting from D10, the Mac ID data are stored in the order as below.
D10
16#1234
16#5678
4.
If the already-power-on time is 70000 minutes (16#00011170), the reading code of the instruction is 2 and the read
data are stored in the devices starting from D20, the already-power-on time data are stored in the order as below.
D20
16#1170
16#0001
5.
Only the first-time execution of the INFO instruction is effective when the conditional contact is met. Therefore, it is
recommended to use the pulse instruction INFOP. If the INFO instruction is used with the normally-open contact
together, the instruction will be automatically executed only once.
Additional remark:
If D is declared in a variable and the code is 0, 1 and 2, they can be declared respectively in ARRAY [9], [3], [2] of
WORD.
D2
D3
16#5432
16#412D
16#3157
'T2'
'A-'
'1W'
D11
D12
16#9ABC
D21
Ch ap te r 6 Ap pl ie d Instruc ti ons
D4
D5
D6
16#3336
16#3036
'36'
'06'
D7
D8
16#3030
16#0031
'00'
'1'
6 - 7 3 5
6_