Delta AS Series Programming Manual page 980

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Symbol
Explanation
1.
S
is the serial number of the module at the right of the PLC. The first one is number 1, the second one is number 2
1
and so on. Whatever modules at the right of the PLC must be numbered. The setting range is 1~32. If the setting
value (<1 or >32) exceeds the range, the instruction will run at the minimum value or maximum value.
2.
S
is the DeviceNet Mac ID within the range: 0~63. It can be the Mac ID of the slave which the master is to read and
2
write as well as the Mac ID of the master which means to read and write the data in the master.
3.
S
is the DeviceNet service code.
3
Service code
4.
S
S
and S
are respectively class ID, instance ID and attribute ID for specifying the parameter path in the EPATH
4,
5
6
of the DeviceNet protocol.
S
:
1
S
:
2
S
:
3
S
:
4
S
:
5
S
:
6
S
:
7
S
:
8
S
:
9
S
:
10
D
:
1
D
:
2
D
:
3
D
:
4
D
:
5
0x01
0x02
0x0E
0x10
Cha p ter 6 App l ied Ins truc tio ns
Number of the module sending the DeviceNet
communication
DeviceNet MAC ID
Service Code
Class ID
Instance ID
Attribute ID
Written-data length
Device for storing written data
Communication timeout time
Number of times of retransmission
Completion flag
Error flag
Error code
Read-data length
Device for storing read data
Description
Read all attributes (Get_Attribute_All)
Set all attributes (Set_Attribute_All)
Read one single attribute
(Get_Attribute_Single)
Set one single attribute (Set_Attribute_Single)
6_
6 - 7 0 1

Hide quick links:

Advertisement

Table of Contents
loading