A S S er i es Pr og r am m ing M an u a l
API
Instruction code
1107
D
Device
X
S
D
n
Data
type
S
D
n
Symbol
_6
Explanation
1.
For this instruction, the length of the data is the value in the device specified by S, and the data itself is in the
devices specified by S+1–S+(the value in S). This instruction stores the data in the device specified by S+n in D
and deletes it, shifts the data in the devices specified by S+n+1–S+(The value in S) to the right, clears the data in
the device specified by S+(the value in S) to 0, and decrements the value in the device specified by S by one.
When the value in the device specified by S is equal to 0, the instruction stops deleting the data, and sets the zero
flag SM600 is ON.
2.
In general, the SFDELP pulse instruction is used.
6 - 3 3 2
SFDEL
P
Y
M
S
T
Operand
S, D, n
C
HC
D
FR
SM
Pulse instruction
AS
S : First device
D : Device where the data is stored
n : Device where the data is deleted
Function
Deleting data from a data list
SR
E
K
16#
16-bit instruction
32-bit instruction
AS
"$"
F
AS

Hide quick links: