Siemens SINAMICS G120 List Manual page 92

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p0585
Measuring probe gear factor / Probe gear factor
CU240E-2
Access level: 3
CU240E-2_DP
Can be changed: U, T
CU240E-2 PN
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
0.00000
CU240E-2_DP_F
Description:
Sets the BERO gear factor.
The measured speed is multiplied by the BERO gear factor and is displayed in r0586.
r0586
CO: Measuring probe speed actual value / MT n_act
CU240E-2
Access level: 3
CU240E-2_DP
Can be changed: -
CU240E-2 PN
Unit group: 3_1
CU240E-2_F
Min
CU240E-2_PN_F
- [rpm]
CU240E-2_DP_F
Description:
Displays the speed actual value measured using the BERO.
Dependency:
Refer to: p0580, p0583
Note:
For p0580 = 0 (no measuring probe), a value of zero is displayed here.
r0587
CO: Measuring probe measuring time measured / MT t_meas measured
CU240E-2
Access level: 3
CU240E-2_DP
Can be changed: -
CU240E-2 PN
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
-
CU240E-2_DP_F
Description:
Displays the time between the last two BERO pulses.
The measuring time is specified as 32-bit value with a resolution of 1/48 µs.
If a new pulse is not received before the maximum measured time in p0583 expires, then r0587 is set to the
maximum measuring time.
Dependency:
Refer to: p0580
Note:
For p0580 = 0 (no measuring probe), a value of zero is displayed here.
r0588
CO: Measuring probe pulse counter / MT pulse counter
CU240E-2
Access level: 3
CU240E-2_DP
Can be changed: -
CU240E-2 PN
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
-
CU240E-2_DP_F
Description:
Displays the number of measuring pulses that have occurred (been received) up until now.
Dependency:
Refer to: p0580
Note:
After reaching 4294967295 (2^32 - 1), the counter starts again at 0.
92
Calculated: -
Scaling: -
Unit selection: -
Max
1000.00000
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
1.00000
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [rpm]
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
List Manual (LH11), 01/2016, A5E33839529