p2265
Technology controller actual value filter time constant / Tec_ctrl act T
Access level: 2
Can be changed: U, T
Unit group: -
Min
0.000 [s]
Description:
Sets the time constant for the actual value filter (PT1) of the technology controller.
r2266
CO: Technology controller actual value after filter / Tec_ctr act aftFlt
Access level: 3
Can be changed: -
Unit group: 9_1
Min
- [%]
Description:
Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
p2267
Technology controller upper limit actual value / Tec_ctrl u_lim act
Access level: 3
Can be changed: U, T
Unit group: 9_1
Min
-200.00 [%]
Description:
Sets the upper limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value exceeds this upper limit, this results in fault F07426.
p2268
Technology controller lower limit actual value / Tec_ctrl l_lim act
Access level: 3
Can be changed: U, T
Unit group: 9_1
Min
-200.00 [%]
Description:
Sets the lower limit for the actual value signal of the technology controller.
Dependency:
Refer to: p2264, p2265, p2271
Refer to: F07426
Notice:
If the actual value falls below this lower limit, this results in fault F07426.
p2269
Technology controller gain actual value / Tech_ctrl gain act
Access level: 3
Can be changed: U, T
Unit group: -
Min
0.00 [%]
Description:
Sets the scaling factor for the actual value of the technology controller.
Dependency:
Refer to: p2264, p2265, p2267, p2268, p2271
Note:
For 100%, the actual value is not changed.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
200.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
500.00 [%]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
-100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]