Siemens SINAMICS G120 List Manual page 133

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Note:
The signal via BI: p0858 (unconditionally close holding brake) has a higher priority than via BI: p0855 (unconditionally
open holding brake).
For a 1 signal via BI: p0858, the command "unconditionally close the holding brake" is executed and internally a zero
setpoint is entered.
p0860
BI: Line contactor feedback signal / Line contact feedb
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the feedback signal from the line contactor.
Recommendation:
When the monitoring is activated (BI: p0860 not equal to r0863.1), then to control the line contactor, signal BO:
r0863.1 of its own drive object should be used.
Dependency:
Refer to: p0861, r0863
Refer to: F07300
Notice:
The line contactor monitoring is de-activated if the control signal of the particular drive object is set as the signal
source for the feedback signal of the line contactor (BI: p0860 = r0863.1).
Note:
The state of the line contactor is monitored depending on signal BO: r0863.1.
When the monitoring is activated (BI: p0860 not equal to r0863.1), fault F07300 is then also output if the contactor is
closed before it is controlled using r0863.1.
p0861
Line contactor monitoring time / LineContact t_mon
Access level: 3
Can be changed: T
Unit group: -
Min
0 [ms]
Description:
Sets the monitoring time of the line contactor.
This time starts each time that the line contactor switches (r0863.1). If a feedback signal is not received from the line
contactor within the time, a message is output.
Dependency:
Refer to: p0860, r0863
Refer to: F07300
Note:
The monitoring function is disabled for the factory setting of p0860.
r0863.0...1
CO/BO: Drive coupling status word/control word / CoupleZSW/STW
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Display and BICO output for the status word and control word of the drive coupling.
Bit field:
Bit
00
01
Note:
For bit 01:
Bit 1 is used to control an external line contactor.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Signal name
Closed-loop control operation
Energize contactor
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
5000 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
2 Parameters
2.2 List of parameters
Data type: U32 / Binary
Dyn. index: -
Func. diagram: 2634
Factory setting
863.1
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2634
Factory setting
100 [ms]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
FP
-
2634
133