Table 2-2
Possible combinations of BICO interconnections, continued
BICO output parameter
BO: Unsigned8
BO: Unsigned16
BO: Unsigned32
BO: Integer16
BO: Integer32
BO: FloatingPoint32
Legend:
Can be changed
The "-" sign indicates that the parameter can be changed in any object state and that the
change will be effective immediately.
The information "C(x), T, U" ((x): optional) means that the parameter can be changed only in
the specified drive unit state and that the change will not take effect until the unit switches to
another state. This can be a single state or multiple states.
The following states are available:
• C(x) commissioning
• U
• T
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Unsigned32 /
Integer16
x :
BICO interconnection permitted
–:
BICO interconnection not permitted
rxxxx:
BICO interconnection is only permitted for the specified CO parameters
Drive commissioning is in progress (p0010 > 0).
Pulses cannot be enabled.
The parameter can only be changed in the following drive commissioning settings
(p0010 > 0):
• C: Can be changed for all settings p0010 > 0.
• C(x): Can only be changed for the settings p0010 = x.
A modified parameter value does not take effect until drive commissioning mode is
exited with p0010 = 0.
Operation
Pulses are enabled.
Ready
The pulses are not enabled and the status "C(x)" is not active.
BICO input parameter
CI parameter
Unsigned32 /
Unsigned32 /
Integer32
FloatingPoint32
C: Commissioning
U: Run
T: Ready to run
2 Parameters
2.1 Overview of parameters
BI parameter
Unsigned32 /
Binary
x
x
x
x
x
17