2 Parameters
2.2 List of parameters
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
For drives with closed-loop torque control (activated using p1501), the following applies:
BI: p0848 = 0 signal:
- no dedicated braking response, but pulse suppression when standstill is detected (p1226, p1227).
p0849[0...n]
BI: No Quick Stop / Quick Stop (OFF3) signal source 2 / OFF3 S_src 2
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the second signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switching-on inhibited)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- no OFF3 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is effective.
Note:
For drives with closed-loop torque control (activated using p1501), the following applies:
BI: p0849 = 0 signal:
- no dedicated braking response, but pulse suppression when standstill is detected (p1226, p1227).
p0852[0...n]
BI: Enable operation/inhibit operation / Operation enable
CU240B-2_DP
Access level: 3
CU240E-2_DP
Can be changed: T
CU240E-2 PN
Unit group: -
CU240E-2_PN_F
Min
CU240E-2_DP_F
-
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
BI: p0852 = 0 signal
Inhibit operation (suppress pulses).
BI: p0852 = 1 signal
Enable operation (pulses can be enabled).
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0852[0...n]
BI: Enable operation/inhibit operation / Operation enable
CU240B-2
Access level: 3
CU240E-2
Can be changed: T
CU240E-2_F
Unit group: -
Min
-
Description:
Sets the signal source for the command "enable operation/inhibit operation".
For the PROFIdrive profile, this command corresponds to control word 1 bit 3 (STW1.3).
130
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
[0] 2090.3
[1] 1
[2] 2090.3
[3] 2090.3
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
1
List Manual (LH11), 01/2016, A5E33839529