2 Parameters
2.2 List of parameters
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
In addition to all of the combinations listed above, using bit 7, the "STO via Power Module terminals" function can be
enabled (this is permissible for r9771.19 = 1).
Bit field:
Bit
00
03
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change only becomes effective after a POWER ON.
STO: Safe Torque Off
p9801
SI enable functions integrated in the drive (processor 2) / SI enable fct P2
PM230_STO
Access level: 3
CU240E-2
Can be changed: C(95)
CU240E-2_F
Unit group: -
Min
-
Description:
Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 2.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
0001 hex:
Basic functions are enabled via onboard terminals (permissible for r9771.0 = 1).
0004 hex:
Extended functions are enabled via onboard terminals (permissible for r9771.5 = 1).
0008 hex:
Basic functions are enabled via PROFIsafe (permissible for r9771.6 = 1).
0009 hex:
Basic functions are enabled via PROFIsafe onboard terminals (permissible for r9771.6 = 1).
000C hex:
Extended functions are enabled via PROFIsafe (permissible for r9771.4 = 1).
000D hex:
Extended functions are enabled via PROFIsafe and basic functions via onboard terminals (permissible for r9771.4 =
1).
In addition to all of the combinations listed above, using bit 7, the "STO via Power Module terminals" function can be
enabled (this is permissible for r9771.19 = 1).
Bit field:
Bit
00
Dependency:
Refer to: p9601, r9871
Notice:
This parameter is overwritten by the copy function of the safety functions integrated in the drive.
Note:
A change only becomes effective after a POWER ON.
STO: Safe Torque Off
p9801
SI enable functions integrated in the drive (processor 2) / SI enable fct P2
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2
Min
-
Description:
Sets the enable signals for the safety functions integrated in the drive and the type of selection on processor 2.
Not all of the settings listed below will be permissible, depending on the Control Unit and Power Module being used:
0000 hex:
Safety functions integrated in the drive inhibited (no safety function).
442
Signal name
Enable STO via terminals (processor 2)
Enable PROFIsafe (processor 2)
Signal name
Enable STO via terminals (processor 2)
1 signal
Enable
Enable
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Enable
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU240B-2/CU240E-2
0 signal
Inhibit
Inhibit
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0000 bin
0 signal
Inhibit
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0000 0000 bin
List Manual (LH11), 01/2016, A5E33839529