4 Faults and alarms
4.1 Overview of faults and alarms
Table 4-2
Fault reactions, continued
List
PROFIdrive
OFF2
COAST
STOP
OFF3
QUICK
STOP
STOP2
-
IASC/
-
DCBRAKE
766
Reaction
Internal/external
Closed-loop speed and torque control
pulse disable
• Instantaneous pulse suppression, the drive "coasts" to a standstill.
• The motor holding brake (if one is being used) is closed
immediately.
• Switching-on inhibited is activated.
Brake along the
Closed loop speed control (p1300 = 20, 21)
OFF3 down ramp
• n_set = 0 is input immediately to brake the drive along the OFF3
followed by pulse
ramp down (p1135).
disable
• When zero speed is detected, the motor holding brake (if
parameterized) is closed. The pulses are suppressed when the
holding brake's closing time (p1217) expires.
Zero speed is detected if the actual speed drops below the
threshold in p1226 or if the monitoring time (p1227) started when
speed setpoint <= speed threshold (p1226) has expired.
• Switching-on inhibited is activated.
Torque control (p1300 = 22, 23)
• Changeover to speed-controlled operation and other reactions as
described for speed-controlled operation.
n_set = 0
• n_set = 0 is input immediately to brake the drive along the OFF3
ramp down (p1135).
• The drive remains in closed-loop speed control.
-
• For synchronous motors, the following applies:
If a fault occurs with this fault reaction, an internal armature short-
circuit is triggered.
The conditions for p1231 = 4 must be observed.
• For induction motors, the following applies:
If a fault occurs with this fault reaction, DC braking is triggered.
DC braking must have been commissioned (p1230 to p1239).
Description
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529