2 Parameters
2.2 List of parameters
r0080[0...1]
CO: Torque actual value / M_act
Access level: 3
Can be changed: -
Unit group: 7_1
Min
- [Nm]
Description:
Display and connector output for actual torque value.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0031, p0045
Note:
The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
r0081
CO: Torque utilization / M_Utilization
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the torque utilization as a percentage.
The torque utilization is obtained from the required smoothed torque referred to the torque limit.
Dependency:
This parameter is only available for vector control. For U/f control r0081 = 0 %.
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: r0033
Note:
The torque utilization is available smoothed (r0033) and unsmoothed (r0081).
The torque utilization is obtained from the required torque referred to the torque limit as follows:
- Positive torque: r0081 = (r0079 / r1538) * 100 %
- Negative torque: r0081 = (-r0079 / -r1539) * 100 %
r0082[0...2]
CO: Active power actual value / P_act
Access level: 3
Can be changed: -
Unit group: 14_5
Min
- [kW]
Description:
Displays the instantaneous active power.
Index:
[0] = Unsmoothed
[1] = Smoothed with p0045
[2] = Electric power
Dependency:
Refer to: r0032
Note:
The mechanical active power is available smoothed (r0032 with 100 ms, r0082[1] with p0045) and unsmoothed
(r0082[0]).
r0083
CO: Flux setpoint / Flex setp
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the flux setpoint.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
48
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: r2004
Unit selection: p0505
Max
- [kW]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6714, 6799
Factory setting
- [Nm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 8012
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6714, 6799
Factory setting
- [kW]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5722
Factory setting
- [%]
List Manual (LH11), 01/2016, A5E33839529