Siemens SINAMICS G120 List Manual page 422

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
p9672
SI module identifier Power Module / Module ID PM
PM230_STO
Access level: 3
PM240
Can be changed: C(95), T
PM250
Unit group: -
PM260
Min
CU240E-2
0
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
CRC via the Node Identifier of a Power Module.
Note:
PM: Power Module
p9700
SI copy function / SI copy function
PM230_STO
Access level: 3
PM240
Can be changed: C(95), U, T
PM250
Unit group: -
PM260
Min
CU240E-2
0000 hex
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Setting to start the required copy function.
After starting, the corresponding parameters are copied from processor 1 to processor 2.
Once copying is complete, the parameter is automatically reset to zero.
Value:
0:
29:
87:
208:
Dependency:
Refer to: r3996
Notice:
When the parameters are copied, short-term communication interruptions may occur.
Note:
For value = 57 hex and D0 hex:
The value can only be set if the safety commissioning mode is set and the Safety Integrated password was entered.
For value = D0 hex:
The following parameters are copied after starting the copy function:
p9601 --> p9801, p9610 --> 9810, p9650 --> p9850, p9651 --> p9851
p9701
Acknowledge SI data change / Ackn SI data
PM230_STO
Access level: 3
PM240
Can be changed: C(95), U, T
PM250
Unit group: -
PM260
Min
CU240E-2
0000 hex
CU240E-2_DP
CU240E-2 PN
CU240E-2_F
CU240E-2_PN_F
CU240E-2_DP_F
Description:
Setting to transfer the reference checksums from the associated actual checksums after changes (SI parameters,
hardware).
After transferring the reference checksums, parameters are automatically reset to zero.
422
[00 hex] Copy function ended
[1D hex] Start copy function node identifier
[57 hex] Start copy function SI parameters
[D0 hex] Start copy function SI basic parameters
Calculated: -
Scaling: -
Unit selection: -
Max
4294967295
Calculated: -
Scaling: -
Unit selection: -
Max
00D0 hex
Calculated: -
Scaling: -
Unit selection: -
Max
00EC hex
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0000 hex
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0000 hex