Siemens SINAMICS G120 List Manual page 62

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

2 Parameters
2.2 List of parameters
Dependency:
When selecting p0300 = 10 ... 19, parameters p0335, p0626, p0627, and p0628 of the thermal motor model are pre-
assigned as a function of p0307 and p0311.
For p0096 = 1 (Standard Drive Control) synchronous motor types cannot be selected.
Caution:
If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
Notice:
If a catalog motor is selected (p0300 >= 100) and an associated motor code number (p0301), then the parameters
that are associated with this list cannot be changed (write protection). The write protection is canceled if the motor
type p0300 is set to a non-Siemens motor that matches p0301 (e.g. p0300 = 1 for p0301 = 1xxxx). Write protection is
automatically canceled when the results of motor data identification are copied to the motor parameters.
The motor type of a catalog motor corresponds to the upper three digits of the code number or the following
assignment (if the particular motor type is listed):
Type/code number ranges
100 / 100xx, 110xx, 120xx, 130xx, 140xx, 150xx
108 / 108xx, 118xx, 128xx, 138xx, 148xx, 158xx
271 / 271xx, 281xx
277 / 277xx, 287xx, 297xx
Note:
Once the Control Unit has been switched on for the first time or if the factory settings have been defined accordingly,
the motor type is pre-configured to induction motor (p0300 = 1).
If a motor type has not been selected (p0300 = 0), then the drive commissioning routine cannot be exited.
A motor type with a value above p0300 >= 100 describes motors for which a motor parameter list exists.
p0300[0...n]
Motor type selection / Mot type sel
PM250
Access level: 2
PM260
Can be changed: C(1, 3)
Unit group: -
Min
0
Description:
Selecting the motor type.
The first digit of the parameter value always defines the general motor type and corresponds to the third-party motor
belonging to a motor list:
1 = induction motor
2 = synchronous motor
xx = motor without code number
xxx = motor with code number
The type information must be entered to filter motor-specific parameters and to optimize the operating characteristics
and behavior. For example, for synchronous motors, power factor (p0308) is neither used nor displayed (in the
BOP/IOP).
The following applies for values < 100:
Motor data must be manually entered.
The following applies for values >= 100:
Motor data are automatically loaded from an internal list.
Value:
0:
1:
2:
10:
13:
17:
19:
100:
101:
271:
277:
Dependency:
When selecting a motor type from the 1LA7 series, parameters p0335, p0626, p0627, and p0628 of the thermal
motor model are pre-assigned as a function of p0307 and p0311.
Caution:
If a motor is selected, which is not contained in the motor lists (p0300 < 100), then the motor code number must be
reset (p0301 = 0), if previously a motor was parameterized from the motor list.
62
No motor
Induction motor
Synchronous motor
1LE1 induction motor (not a code number)
1LG6 induction motor (not a code number)
1LA7 induction motor (not a code number)
1LA9 induction motor (not a code number)
1LE1 induction motor
1PC1 induction motor
1FG1 synchronous geared motor without encoder
1FK7 synchronous motor without encoder
Calculated: -
Scaling: -
Unit selection: -
Max
277
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: Integer16
Dyn. index: MDS, p0130
Func. diagram: 6310
Factory setting
0
List Manual (LH11), 01/2016, A5E33839529

Advertisement

Table of Contents
loading

Table of Contents