r0084[0...1]
CO: Flux actual value / Flux act val
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the flux actual value.
Index:
[0] = Unsmoothed
[1] = Smoothed
r0087
CO: Actual power factor / Cos phi act
Access level: 3
Can be changed: -
Unit group: -
Min
-
Description:
Displays the actual active power factor.
This value refers to the electrical power of the basic fundamental signals at the output terminals of the converter.
r0089[0...2]
Actual phase voltage / U_phase act val
Access level: 4
Can be changed: -
Unit group: 5_3
Min
- [V]
Description:
Displays the actual phase voltage.
Index:
[0] = Phase U
[1] = Phase V
[2] = Phase W
Note:
The values are determined from the transistor switch-on duration.
r0094
CO: Transformation angle / Transformat_angle
Access level: 3
Can be changed: -
Unit group: -
Min
- [°]
Description:
Displays the transformation angle.
Dependency:
Refer to: r1778
Note:
The transformation angle corresponds to the electrical commutation angle.
p0096
Application class / Appl_class
PM240
Access level: 1
Can be changed: C(1)
Unit group: -
Min
0
Description:
Setting the commissioning and control view for various application classes.
Value:
0:
1:
2:
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Expert
Standard Drive Control (SDC)
Dynamic Drive Control (DDC)
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [V]
Calculated: -
Scaling: p2005
Unit selection: -
Max
- [°]
Calculated: -
Scaling: -
Unit selection: -
Max
2
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6730, 6731
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6719
Factory setting
- [V]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [°]
Data type: Integer16
Dyn. index: -
Func. diagram: 6019
Factory setting
0