2 Parameters
2.2 List of parameters
Dependency:
Refer to: r0026
Notice:
When measuring a DC link voltage < 200 V, for the Power Module a valid measured value is not supplied. In this
case, when an external 24 V power supply is connected, a value of approx. 24 V is displayed in the display
parameter.
Note:
The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0071
Maximum output voltage / U_output max
Access level: 3
Can be changed: -
Unit group: 5_1
Min
- [Vrms]
Description:
Displays the maximum output voltage.
Dependency:
The maximum output voltage depends on the actual DC link voltage (r0070) and the maximum modulation depth
(p1803).
Note:
As the (driven) motor load increases, the maximum output voltage drops as a result of the reduction in DC link
voltage.
r0072
CO: Output voltage / U_output
Access level: 3
Can be changed: -
Unit group: 5_1
Min
- [Vrms]
Description:
Display and connector output for the actual output voltage of the power unit.
Dependency:
Refer to: r0025
Note:
The output voltage is available smoothed (r0025) and unsmoothed (r0072).
r0073
Maximum modulation depth / Modulat_depth max
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the maximum modulation depth.
Dependency:
Refer to: p1803
r0074
CO: Modulat_depth / Mod_depth
Access level: 4
Can be changed: -
Unit group: -
Min
- [%]
Description:
Display and connector output for the actual modulation depth.
Dependency:
Refer to: r0028
Note:
For space vector modulation, 100% corresponds to the maximum output voltage without overcontrol.
Values above 100 % indicate an overcontrol condition - values below 100% have no overcontrol.
The phase voltage (phase-to-phase, rms) is calculated as follows:(r0074 x r0070) / (sqrt(2) x 100 %).
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
46
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6301, 6640, 6700,
6722, 6723, 6724, 6725, 6727
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5700, 6730, 6731,
6799
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6723, 6724
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 5730, 6730, 6731,
6799, 8940, 8950
Factory setting
- [%]
List Manual (LH11), 01/2016, A5E33839529