p0634[0...n]
Q flux flux constant unsaturated / PSIQ KPSI UNSAT
Access level: 3
Can be changed: C(3), U, T
Unit group: -
Min
0.000 [Vsrms]
Description:
The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
The parameter weights the unsaturated component of the quadrature axis flux function.
p0635[0...n]
Q flux quadrature axis current constant unsaturated / PSIQ KIQ UNSAT
Access level: 3
Can be changed: C(3), U, T
Unit group: -
Min
0.00 [Arms]
Description:
The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the interdependency of the unsaturated component of the quadrature axis current.
Dependency:
Refer to: p0634
p0636[0...n]
Q flux direct axis current constant unsaturated / PSIQ KID UNSAT
Access level: 3
Can be changed: C(3), U, T
Unit group: -
Min
0.00 [Arms]
Description:
The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the interdependency of the unsaturated component of the direct axis current.
Dependency:
Refer to: p0634
p0637[0...n]
Q flux flux gradient saturated / PSIQ Grad SAT
Access level: 3
Can be changed: C(3), U, T
Unit group: -
Min
0.00 [mH]
Description:
The non-linear and cross-coupled quadrature axis flux functions are defined using 4 coefficients.
This parameter describes the gradients of the saturated component over the quadrature axis current.
Dependency:
Refer to: p0634, p0635, p0636
p0640[0...n]
Current limit / Current limit
Access level: 2
Can be changed: C(1, 3), U, T
Unit group: -
Min
0.00 [Arms]
Description:
Sets the current limit.
Dependency:
Refer to: r0209, p0323
Note:
The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0305. The current limit p0640 is limited to r0209.
The resulting current limit is displayed in r0067 and if required, r0067 is reduced by the thermal model of the power
unit.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: -
Unit selection: -
Max
100.000 [Vsrms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.00 [mH]
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
10000.00 [Arms]
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.000 [Vsrms]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00 [Arms]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00 [Arms]
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: -
Factory setting
0.00 [mH]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6640
Factory setting
0.00 [Arms]
103

Advertisement

Table of Contents
loading

Table of Contents