Siemens SINAMICS G120 List Manual page 51

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Dependency:
For standard induction motors (p0301 > 10000), bit 0 is automatically pre-assigned the connection type of the
selected data set.
For p0100 > 0 (60 Hz rated motor frequency), it is not possible to select bit 1.
Refer to: p0304, p0305, p1082
Note:
For bit 00:
When changing the bits, the rated motor voltage p0304 and the rated motor current p0305 are automatically
converted to the selected connection type (star/delta).
For bit 01:
87 Hz operation is only possible in the delta connection type. When selected, the maximum speed p1082 is
automatically pre-assigned for a maximum output frequency of 87 Hz.
p0170
Number of Command Data Sets (CDS) / CDS count
Access level: 2
Can be changed: C(15)
Unit group: -
Min
2
Description:
Sets the number of Command Data Sets (CDS).
Dependency:
Refer to: p0010, r3996
Notice:
When the data sets are created, short-term communication interruptions may occur.
Note:
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0180
Number of Drive Data Sets (DDS) / DDS count
Access level: 3
Can be changed: C(15)
Unit group: -
Min
1
Description:
Sets the number of Drive Data Sets (DDS).
Dependency:
Refer to: p0010, r3996
Notice:
When the data sets are created, short-term communication interruptions may occur.
r0197[0...1]
Bootloader version / Bootloader vers
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Displays the bootloader version.
Index 0:
Displays the bootloader version.
Index 1:
Displays the bootloader version 3 (for CU320-2 and CU310-2)
Value 0 means that boot loader 3 is not available.
Dependency:
Refer to: r0018, r0198
Note:
Example:
The value 1010100 should be interpreted as V01.01.01.00.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: -
Unit selection: -
Max
4
Calculated: -
Scaling: -
Unit selection: -
Max
4
Calculated: -
Scaling: -
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8560
Factory setting
2
Data type: Unsigned8
Dyn. index: -
Func. diagram: 8565
Factory setting
1
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
51