Dependency:
The selection of the total speed setpoint is automatically interconnected to the status word of the technology
controller (r2349.4) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
Refer to: p1109
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to withdraw the
interconnection to its status word (r2349.4).
p1109[0...n]
CI: Total setpoint / Total setp
Access level: 4
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the total setpoint.
For p1108 = 1 signal, the total setpoint is read in via p1109.
Dependency:
The signal source of the total setpoint is automatically interconnected to the output of the technology controller
(r2294) if the technology controller is selected (p2200 > 0) and operated in the mode p2251 = 0.
Refer to: p1108
Caution:
If the technology controller is to supply the total setpoint using p1109, then it is not permissible to disable the
interconnection to its output (r2294).
p1110[0...n]
BI: Inhibit negative direction / Inhib neg dir
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to disable the negative direction.
Dependency:
Refer to: p1111
p1111[0...n]
BI: Inhibit positive direction / Inhib pos dir
Access level: 3
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source to disable the positive direction.
Dependency:
Refer to: p1110
r1112
CO: Speed setpoint after minimum limiting / n_set aft min_lim
Access level: 4
Can be changed: -
Unit group: 3_1
Min
- [rpm]
Description:
Displays the speed setpoint after the minimum limiting.
Dependency:
Refer to: p1091, p1092, p1093, p1094, p1101
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
2 Parameters
2.2 List of parameters
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3030
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2505, 3040
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2505, 3040
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 3050
Factory setting
- [rpm]
165