p1525[0...n]
CO: Torque limit lower scaling / M_max lower scal
Access level: 3
Can be changed: U, T
Unit group: -
Min
-2000.0 [%]
Description:
Sets the scaling for the lower torque limit.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Notice:
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note:
This parameter can be freely interconnected.
The value has the meaning stated above if it is interconnected from connector input p1528.
r1526
CO: Torque limit upper without offset / M_max up w/o offs
Access level: 3
Can be changed: -
Unit group: 7_1
Min
- [Nm]
Description:
Display and connector output for the upper torque limit of all torque limits without offset.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
r1527
CO: Torque limit lower without offset / M_max low w/o offs
Access level: 3
Can be changed: -
Unit group: 7_1
Min
- [Nm]
Description:
Display and connector output for the lower torque limit of all torque limits without offset.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Refer to: p1520, p1521, p1522, p1523, p1528, p1529
p1528[0...n]
CI: Torque limit upper scaling / M_max upper scal
Access level: 4
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the scaling of the upper torque limit in p1522.
Dependency:
Not visible with application class: "Standard Drive Control" (SDC, p0096 = 1)
Danger:
For p1400.4 = 0 (torque limiting, upper/lower) the following applies:
Negative values resulting from the signal source and scaling can cause the motor to accelerate in an uncontrolled
manner.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1529[0...n]
CI: Torque limit lower scaling / M_max lower scal
Access level: 4
Can be changed: T
Unit group: -
Min
-
Description:
Sets the signal source for the scaling of the lower torque limit in p1523.
SINAMICS G120 Control Units CU240B-2/CU240E-2
List Manual (LH11), 01/2016, A5E33839529
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
2000.0 [%]
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
Calculated: -
Scaling: p2003
Unit selection: p0505
Max
- [Nm]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
2 Parameters
2.2 List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 6630
Factory setting
100.0 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6060, 6630, 6640
Factory setting
- [Nm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6060, 6630, 6640
Factory setting
- [Nm]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6630
Factory setting
1524[0]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 6630
Factory setting
1525[0]
229