2 Parameters
2.2 List of parameters
r9976[0...7]
System utilization / Sys util
Access level: 3
Can be changed: -
Unit group: -
Min
- [%]
Description:
Displays the system utilization.
If the utilization is greater than 100%, fault F01054 is output.
Index:
[0] = Reserved
[1] = Computing time utilization
[2] = Reserved
[3] = Reserved
[4] = Reserved
[5] = Largest total utilization
[6] = Reserved
[7] = Reserved
Dependency:
Refer to: F01054, F01205
Note:
For index 1:
The value shows the total computing time load of the system.
For index 5:
The total utilization is determined using all sampling times used. The largest total utilization is mapped here. The
sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
r9999[0...99]
Software error internal supplementary diagnostics / SW_err int diag
Access level: 4
Can be changed: -
Unit group: -
Min
-
Description:
Diagnostics parameter to display additional information for internal software errors.
Note:
Only for internal Siemens troubleshooting.
p10002
SI Motion F-DI changeover discrepancy time (processor 1) / SI Mtn DI chg t P1
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
1.00 [ms]
CU240E-2_DP_F
Description:
Sets the discrepancy time for digital inputs.
The signal states at the two associated digital inputs (F-DI) must assume the same state within this discrepancy time.
Dependency:
Refer to: p10102
p10006
SI Motion acknowledgment internal event F-DI (processor 1) / SI Mtn ackn int P1
PM240
Access level: 3
PM250
Can be changed: C(95)
PM260
Unit group: -
CU240E-2_F
Min
CU240E-2_PN_F
0
CU240E-2_DP_F
Description:
Select a fail-safe digital input (F-DI) for the signal "acknowledge internal event" (internal fault).
452
Calculated: -
Scaling: -
Unit selection: -
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
2000.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
255
SINAMICS G120 Control Units CU240B-2/CU240E-2
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [%]
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
500.00 [ms]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
List Manual (LH11), 01/2016, A5E33839529

Advertisement

Table of Contents
loading

Table of Contents